Hard drawn copper tubing should be used where no
appreciable amount of bending around pipes or other
obstructions is necessary. Use long radius ells wherever
possible with one exception. Use short radius ells for traps
in all vertical suction risers. If soft copper must be used,
avoid sharp bends, which may cause a restriction.
Fiberglass insulation and a sealing material such as
permagum should be packed around refrigerant lines where
they penetrate a wall to reduce vibration and to retain some
flexibility.
Support all refrigerant lines at minimum intervals with
suitable hangers, brackets or clamps. Braze all
copper-to-copper joints with Sil-Fos 5 or equivalent brazing
material. Do not use soft solder.
Never braze or solder the liquid and suction lines together.
The complete suction line should be insulated with no less
than 1/2" ARMAFLEX or equivalent. If the liquid and suction
lines are to be taped together for support purposes, they
must be completely insulated from one another.
INSTALLING REFRIGERANT MAINS
The units are evacuated and dehydrated at the factory and
shipped with a holding charge of Refrigerant-22. The suction
and liquid connections are sealed with copper discs. Refer
to the appropriate condensing unit installation instructions for
charging data.
DESCRIPTION
UNIT MODEL
060 090 120
EVAPORATOR COIL
Rows Deep x Rows Wide 3 x 24 3 x 27 3 x 32
Finned Length - inches 30 46 46
Face Area - square feet 5.0 8.6 10.2
Tube OD - inches 3/8 3/8 3/8
Fins per inch 13 13 13
CENTRIFUGAL BLOWER
(Forward Curve)
Diameter x Width - inches 10 x 10 15 x 15 15 x 15
MOTORS
1
Nominal HP Rating 3/4 1-1/2 2
FILTERS
(Throwaway)
Quantity Per Unit 16" x 25" x 1" 2 4 4
Face Area - square feet 5.6 11.1 11.1
DISTRIBUTOR One Per Unit 4-3-6-1
2
5-3-10-1
2
5-3-12-1
2
OPERATING
Weight, Lbs.
3
Basic Unit 210 325 330
Accessories
Supply Air Plenum 90 102 102
Return Air Grille 12 15 15
Hot Water Coil 56 82 82
Steam Coil 57 85 85
Base 45 60 60
Electric Heat: 10 KW 60 63 63
16 KW 64 66 66
26 KW 68 71 71
36 KW - 74 74
HOT WATER COIL
Tubes OD, inches 1/2 (Copper)
Rows Deep 2
Fins Per Inch 12 (Aluminum)
Face Area, square feet 3.6 6.8 6.8
Connections (Supply & Return) 1" NPTE
STEAM COIL
Outer Tube OD, inches 1 (Brass)
Rows Deep 1
Fins Per Inch 8 (Aluminum)
Face Area - square feet 3.7 6.6 6.6
Connection
Inlet 1-1/2" NPTE
Outlet 1-1/2" NPTE
ELECTRIC HEAT
Heater
Elements
% Nickel 59.2
%Chromium 16.0
Watt Density,
watts/sq. in.
59.0
Face Area, square feet 3.0
SHIPPING VOLUME - Cubic Feet (Basic Unit) 30 53 53
1
Refer to Blower Motor and Drive Data for additional blower motor and drive information.
2
The first digit refers to inlet diameter (1/8"), second digit refers to tube diameter (1/16") and the third digit refers to number of tubes and the
fourth digit refers to number of distributors.
3
Refer to the unit installation instruction for the distributed weight of the evaporator blower unit:
Form 550.23-N1Y (060, 090 and 120)
TABLE 2
- PHYSICAL DATA
550.23-N2Y
Unitary Products Group 5