LIMITATIONS
This unit must be installed in accordance with all national
and local safety codes. If no local codes apply, installation
must conform to the appropriate national code. The unit is
designed to meet National Safety Code Standards. If
components are to be added to a unit to meet local codes,
they are to be installed at the dealers and/or the customers
expense. See Table 1 for application limitations.
LOCATION
These Evaporator Blowers are not designed for outdoor
installation. They must be located within the building
structure, either inside or outside the conditioned space.
These Evaporator Blower sections allow for vertical or
horizontal installation in any area offering proper electrical
supply, duct and drain connections.
They may be installed either with ductwork or matching
plenum and inlet grille.
The units should be located as close to the condensing units
as practical and positioned to minimize bends in the
refrigerant piping.
Units being installed vertically or horizontally can be set
directly on a floor or platform, or metal or wooden beams
can support them.
Units being installed horizontally can be suspended from
above. Four 3/8" weld nuts are provided in the unit frame to
accommodate hanger rods. Knockouts must be removed
from the unit panels to expose these weld nuts. Refer to
Figure 1 for their location and the individual load on each
hanger rod.
WARNING: Be careful when attaching the hanger rods. They
must not be allowed to turn or slip.
CLEARANCES
Refer to the unit dimension details, Figures 12 and 13 for
clearances required for servicing and for proper unit
operation.
INSTALLATION
Model
Power
Supply
Voltage
Variation*
Supply Air
CFM
Entering Air Temperatures, °F
Cooling Coil - db/wb Heating Coil - db
Min. Max. Min. Max. Min. Max. Min. Max.
K2EU060A06 208/230-1-60 187 252 1600 2400 65/57 95/72 40 77
K4EU090A33
208/230-3-60
460-3-60
187
432
252
504
2400 3600 65/57 95/72 40 77
K3EU120A33
208/230-3-60
460-3-60
187
432
252
504
3200 4800 65/57 95/72 40 77
* Utilization Range "A" in accordance with ARI Standard 110
TABLE 1
- UNIT APPLICATION DATA
34-1/2 (KEU060)
49-1/4 (KEU090, 120)
W1
W4
37-9/16 (KEU060)
44-7/8 (KEU090, 120)
W2
W3
AIR
OUT
AIR
IN
CENTER
OF GRAVITY
1-1/4 (K E U 060)
1-3/8 (K E U 090, 120)
2-5/8
RETURN AIR GRILLE, HOT WATER
COIL AND STEAM COIL
ACCESSORIES INSTALLED ON
ON THIS END OF THE UNIT.
SUPPLY AIR PLENUM AND
ELECTRIC HEATER ACCESSO RIES
INSTALLED ON THIS END OF THE
UNIT.
A
B
(4) 3/8"-16
W ELD NUUTS
Model
Center of Gravity Dimensions (in.) Weight Distribution (Lbs.)
A B W1 W2 W3 W4 TOTAL
KEU060 22-3/8 15-1/4 60 65 40 45 210
KEU090 26-1/4 23-3/4 85 93 70 77 325
KEU120 26-5/8 24-1/8 85 95 70 80 330
FIG. 1
- UNIT SUSPENSION MOUNTING (Horizontal Application)
550.23-N2Y
Unitary Products Group 3
Page view 2